Please use this identifier to cite or link to this item: https://rda.sliit.lk/handle/123456789/663
Title: An electrical PD location method applied to a continuous disc type transformer winding
Authors: Hettiwatte, S. N
Wang, Z. D
Crossley, P. A
Jarman, P
Edwards, G
Darwin, A
Keywords: Electrical PD Location
Method Applied
Continuous Disc Type
Transformer Winding
Issue Date: 1-Jun-2003
Publisher: IEEE
Citation: Cited by 14
Series/Report no.: Proceedings of the 7th International Conference on Properties and Applications of Dielectric Materials (Cat. No. 03CH37417);Vol1 Pages 471-474
Abstract: A 6.6 kV continuous disc type winding of a distribution transformer is used to investigate the propagation of partial discharges (PD) with the aim of location. The winding was modelled, as multiconductor transmission lines with each turn represented by a transmission line. This approach results in the model being valid up to a few MHz in frequency. The validity of the model was confirmed by impedance measurements on the winding. The transfer functions calculated between probable PD source locations to winding terminals showed that the troughs (or zeros) change in frequency with the location of PD source and hence can be used for the location of PD. Transfer functions obtained experimentally using a discharge calibrator as the PD source, showed very good agreement with the calculations.
URI: http://localhost:80/handle/123456789/663
ISSN: 1081-7735
Appears in Collections:Research Papers
Research Papers - Department of Electrical and Electronic Engineering
Research Papers - SLIIT Staff Publications

Files in This Item:
File Description SizeFormat 
An_electrical_PD_location_method_applied_to_a_continuous_disc_type_transformer_winding.pdf
  Until 2050-12-31
280.41 kBAdobe PDFView/Open Request a copy


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.